Most of our induction heating machines are cooled by water, you can build the cooling system for our machines with tap water, water pump and water tank by yourself, we also provide different types of water chiller for you.
Induction heating machine requires water in high quality:
1. good quality water
2. enough pressure
3. small location room
4.Safe And Longtime working
Our water chiller can meet its strict requirements above and prolong your machine working life

CA series chiller specifications:
1.COPELAND compressor,hermetic scroll type,features low noise,low vibration,high efficiency and low energy consumption.
2.Environment-friendly refrigerant,such as R407c,R404a which is no harm to the ozone layer.
3.SCHNEIDER brand electric components will ensure the machine running stably.
4.Imported stainless steel water pump,featuring wide working range,low noise,reliable performance,no leaking and maintenance free.
5.High quality stainless steel tank and pipelines will ensure the water quality and easy to clean maintain.
6.Electric static spraying enclosure,European design and elegant appearance.
working range:
The temperature range of chilled fluid is from 5 to 35degree celsius;
Temperature difference between inlet and outlet chilled fluid is from 3 to 8 degree celsius.
It is better to use the chiller while the ambient temperature at or below 35 degree celsius.
                                  CA Series Air cooled industrial chiller  
                                    Mode
Item
CA-0.6 CA-1 CA-2 CA-3 CA-4 CA-5 CA-6 CA-8(D) CA-10(D)  
nominal cooling capacity Kcal/h
50HZ/60HZ
1290
1548
2451
2941
4446
5332
6803
8163
8815
10578
11223
13468
13115
15738
17630
21156
22446
26935
 
 
KW
50HZ/60HZ
1.5
1.8
2.85
3.42
5.17
6.2
7.91
9.5
10.25
12.3
13.05
15.66
15.25
18.3
20.5
24.6
26.1
31.3
 
 
Total input power KW 0.96 1.46 2.25 3.27 4.57 5.54 6.33 8.29 10.47  
Power supply voltage 1PH~220V 50HZ(60HZ) 3PH 380V 50HZ(220V/415V/480V    50HZ/60HZ)  
(110V 50HZ/60HZ)  
Refrigerant Type R22(R134a/R407C)  
Control mode Capillary Expansion valve  
Compressor Type Hermetic rotating  type Hermetic scroll type(Piston)  
Power(KW) 0.45 0.95 1.73 2.7 3.52 4.41 5.2 3.52× 2 4.41× 2  
Condenser Type High efficient finned copper tube+ low noise outer rotor fan  
Cooling Air volume(m 3 /h) 750 1000 2000 3000 4000 5000 6000 8000 10000  
Evaporator Type Water tank with coil(Shell and Tube)  
Chilled fluid flow(m 3 /h) 0.258
0.31
0.49
0.589
0.89
1.068
1.36
1.63
1.76
2.11
2.24
2.68
2.63
3.15
3.52
4.22
4.47
5.37
 
 
Tank volume(L) 16 20 25 50 60 70 70 120 200  
inlet/outlet pipe caliber 1" 1" 1" 1" 1" 1" 1" 1-1/2" 1-1/2"  
Water pump Power(kw) 0.37 0.37 0.37 0.37 0.75 0.75 0.75 0.75 0.75  
Pump head(m) 20 20 20 20 20 20 20 22 20  
Safty protection Compressor overheating, over current, high and low pressure, over temperature, flow switch, phase sequence, phase-missing, exhaust overheating, anti-freezing.  
Dimension L(mm) 530 580 650 930 1000 1140 1140 1300 1530  
W(mm) 440 440 500 520 560 560 560 720 780  
H(mm) 780 850 950 975 1070 1040 1040 1310 1430  
Weight Kg 50 73 100 135 150 175 180 310 450  
Note:        
1. nominal cooling capacity calculated according to:                                                                                                                                                                                                               Inlet/outlet chilled fluid temperature: 12degree/7degree   Inlet/outlet cooling air temperature: 30degree/35degree                                                                                                            
  2. Working condition:      
  The temperature range of chilled fluid is from 5 to 35degree     Temperature difference between inlet and outlet chilled fluid is from 3 to 8degree,   It is better to run the chiller while the ambient temperature at or below 35degree. The above red parameters is for the particular voltage, which need to made accordingly.          
We reserve the right to modify the above information without further notice.

For more information about our machines, please contact us now for we support you well
 


Water Cooling Chiller for Induction Heating Machine

Water Cooling Chiller for Induction Heating Machine
Water Cooling Chiller for Induction Heating Machine
Water Cooling Chiller for Induction Heating Machine
 

FAQ
Q: What's your advantage? Why we choose you?

A: 1,Our factory has produced the water chiller over 15 years,  we have rich experience in the production and design the water chiller technology machine for customers.

 2, Great production capacity Sustainable Supply . According to customer requirements, We support the customized including the packing

3,  We use 100% new materials and the striclty control for the  production process, in consequence our defective rate is lower than 0.01%

Q: How long is your delivery time?

A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock, it is according to quantity.

Q: How about warranty

A: 12 Months

Q: Do you test all your goods before delivery?
A: Sure, we double test all our machines before delivery

For more questions or details about us and our machines, please contact us as below,

 

 Water Cooling Chiller for Induction Heating Machine
 

DADMAC Monomer Cas:7398-69-8

Polydadmac 40% Cas 26062-79-3,Water Treatment Polydadmac,Dadmac/Dmdaac 60% 65%,Factory Cationic Monomer

ZHEJIANG XINHAITIAN BIO-TECHNOLOGY CO.,LTD. , https://www.dadmacxht.com